Discuss a project →
BA Academy · US fire ratings

Fire-protective or fire-resistive glazing: what is the difference?

BA Academy lesson · about five minutes

Under the IBC and NFPA, which also shape the Saudi Building Code, fire-rated glazing comes in two types. Fire-protective glazing stops flames and smoke, but it lets radiant heat through, so the code limits where and how much of it you can use. Fire-resistive glazing also blocks heat transfer. It is tested as a wall to ASTM E119 or UL 263, and it can be used where fire-protective glazing is not allowed.

By Josh Astin, British Aluminium · Updated 27 November 2026

Fire-protective (opening protectives)

Tested as a window to UL 9 or NFPA 257, or as part of a door to UL 10B, UL 10C or NFPA 252. It is treated as an opening in a rated wall. Because heat passes through, fire-protective glazing in fire windows is generally limited to 25 percent of the wall area. In fire doors serving exit stairs and passageways, vision panels are limited to 100 square inches (0.065 m²).

Fire-resistive (glazing as a wall)

Tested to ASTM E119 or UL 263, the same tests used for solid walls. It limits the temperature rise on the protected side, so it is not held to the 25 percent limit when the framing has the same rating. It is the choice for large glazed walls, stair cores and escape routes. The frame must be tested with it: fire-resistive glass in a fire-protective frame is not a fire-resistive assembly.

How it relates to E, EW and EI

Fire-protective glazing does a similar job to E and EW glazing in Europe, and fire-resistive glazing a similar job to EI. They are similar in purpose, not equivalent. The tests are different, so a rating from one system cannot simply be read as the other.

What to ask the bidder

  • Is the offer fire-protective or fire-resistive?
  • Which test was it listed to (UL 9, UL 10C or UL 263)?
  • Is the frame part of the same listing?

Questions people ask

Is ceramic glass fire-resistive?

Ceramic glass on its own is fire-protective. It does not limit radiant heat.

Does sprinkler protection remove the limits?

Not for fire-protective vision panels in exit-stair doors. Sprinklers change some other requirements, so check the code section.

Related

About British Aluminium

British Aluminium designs and manufactures fire-rated, bullet-resistant, blast-resistant and anti-attack glazing, doors and windows in aluminium and steel. Made in the GCC, for projects in Qatar, Saudi Arabia, Oman and export markets. BA Academy is our series of short lessons for architects, consultants, contractors and procurement teams.

BA products for this

British Aluminium systems where this topic applies.

Comparing offers on a live tender?

Send the specification and the offers you have received. We will tell you which tested systems match the requirement.