What do UL 9 and NFPA 257 test?
BA Academy lesson · about five minutes
UL 9 and NFPA 257 are the US fire tests for window assemblies: fixed or opening glazing in a rated wall, including the frame. The assembly is exposed to a standard fire, then hit with a hose stream to check that it holds together. A pass gives a fire-protection rating, typically 20 to 90 minutes, and the marking OH on the glass.
By Josh Astin, British Aluminium · Updated 27 November 2026
What it measures
Whether flames pass through and whether the assembly stays in place, including after the hose stream. It does not limit heat on the protected side, which is why fire windows are fire-protective and the code restricts their size and location.
Limits to remember
Fire windows in rated walls are generally limited to 25 percent of the wall area they share with a room, and they are commonly rated up to 45 minutes in 1-hour walls. Where a larger area of glass or a higher rating is needed, use fire-resistive glazing tested to UL 263 or ASTM E119.
What to ask the bidder
- Is the window listed to UL 9 or NFPA 257, with the frame?
- Did it pass the hose stream (marking OH)?
- Is the glazed area within the code limit for that wall?
Questions people ask
Is a 20-minute window enough for a 1-hour wall?
Usually not. The code table gives the required rating for each wall type.
Does UL 9 cover doors?
No. Doors are tested to UL 10B, UL 10C or NFPA 252.
Related
About British Aluminium
British Aluminium designs and manufactures fire-rated, bullet-resistant, blast-resistant and anti-attack glazing, doors and windows in aluminium and steel. Made in the GCC, for projects in Qatar, Saudi Arabia, Oman and export markets. BA Academy is our series of short lessons for architects, consultants, contractors and procurement teams.